Isolating Switch 3P
video

Isolating Switch 3P

Isolating switches are mainly used for AC 50Hz, with a rated voltage of 220-1140V and a rated current of 3150A. They are used to isolate circuits and lines that are not frequently connected and disconnected, and are widely applied in power distribution systems and automation systems in industries such as construction, electric power, petrochemical, etc.
Send Inquiry

Description

Technical Parameters

Product Model and Meanings

 

Model and meanings

 

product-1420-760

 

One

NO

and

one

NC

F11

F1 NO +F1NC

Two

NO

and

Two

NC

F22

F2 NO +F2 NC

 

Product Introduction

 

Isolating Switch

1. It adopts a modular design structure, allowing flexible and diverse combinations. Made of glass fiber reinforced unsaturated polyester resin, it has high dielectric performance, a high protection level, and safe and reliable operation. The operating mechanism is an acceleration mechanism with spring energy storage and instantaneous release. The isolating switch has a double-break contact structure for instantaneous connection and disconnection, which is independent of the speed of the operating handle.

2. Isolating switches have various structures and operation modes. They are equipped with a window for directly observing the on-off state of the contacts, allowing operations inside, outside, and at the back of the cabinet, as well as front and side operations, and can be wired at the front and back of the plate.

3. SDKC isolating switches have an attractive, novel, and simple appearance, small size, and complete functions, making them the best choice among similar products.

 

Product Usage Environment

 

Load isolating switches can work under the following conditions:

1. Altitude does not exceed 2500m;

2. Ambient temperature shall not be higher than 40°C or lower than -5°C, and relative humidity shall not exceed 95%;

3. Environment without explosive medium;

4. Environment without rain and snow intrusion;

Note: If the product is expected to be used in an environment where the temperature exceeds +40°C or is lower than -5°C to -45°C, the user shall inform the manufacturer.

 

Product Features

 

1. The acceleration mechanism with spring energy storage and instantaneous release achieves a fast opening speed of (13.8m/s), which is independent of the speed of the operating handle, greatly improving the arc extinguishing capacity.

2. The shell made of glass fiber reinforced unsaturated polyester resin has good flame retardancy, dielectric properties, carbonation resistance, and impact resistance.

3. The parallel double-break contacts have a self-cleaning function.

4. All contact materials of the isolating switch are copper-silver alloy, with two separate contact surfaces.

5. Large isolation distance.

6. When in the "O" position, the switch handle can be locked with three latches at the same time, reliably avoiding misoperation.

 

Technical Parameters

 

Conventional heating current Ith

63A

100A

160A

250A

400A

630A

1000A

1250A

1600A

2000A

2500A

3150A

Rated insulation voltage Ui(V)

750

800

1000

Dielectric strength(V)

3000

3500

Rated impulse withstand voltage Ump(KV)

6

8

12

Rated working voltage Ue(V)

AC400,600

Rated frequency

50Hz

Utlization category

AC-21,22,23

Rated working

current le(A)

AC440V

AC-21

63

100

160

250

400

630

1000

1250

1600

2000

2500

3150

AC-22

63

100

160

250

400

630

1000

1250

1600

2000

2500

3150

AC-23

50

80

160

250

400

630

800

1000

1250

1250

2000

2500

AC660V

AC-21

63

100

160

250

400

630

1000

1250

1600

2000

2500

3150

AC-22

63

80

100

200

315

400

630

630

800

1000

1000

1250

AC-23

40

63

63

125

200

250

250

400

500

1

/

/

Rated making capacity(A)

10le

Rated breaking capacity(A)

8le

Rated short-circuit making capacity lcm(KA)

1.7

1.7

12

17

30

40

70

70

1s shot time withstand current lcw(kA)

3

3

10

12

20

25

50

50

Mechanical life(times)

5000

5000

5000

3000

2000

1000

Electrical life(times)

1000

1000

1000

600

300

/

Operating torque(N.m)

3.5

3.5

6.5

10

15

27

60

Weight (kg)

Without handle)

3P

0.32

0.39

0.88

1.6

3.8

4.2

10.5

10.5

16

31

31

42

4P

0.34

0.41

1.1

2

4.6

5

13

13

20

40

40

49

 

FAQ

 

Q: Can the isolating switch be operated with a load?

A: Isolating switches do not have arc-extinguishing capability, so operation with a load is strictly prohibited. Before operating the isolating switch, it is necessary to ensure that the load current in the circuit has been completely cut off by other equipment with arc-extinguishing capability (such as circuit breakers). Only when the circuit is in a state of no load current can the isolating switch be operated safely.

 

Q: Is professional personnel required for installation?

A: It is recommended to be operated by a certified electrician. Note: When wiring, ensure that the neutral line (N) is correctly connected to the phase line to avoid misjudgment by the frequency converter. An isolating switch must be configured at the incoming line end to meet the safety requirements for maintenance.

 

Q: How to choose a suitable isolating switch?

A: First, determine whether to choose a high-voltage or low-voltage isolating switch according to the voltage level of the actual application scenario.

Second, the rated current needs to be considered. In addition, attention should be paid to the type and structural form of the isolating switch. At the same time, environmental conditions should also be taken into account. For example, isolating switches used outdoors need to have good waterproof, dustproof, and anti-corrosion properties to adapt to harsh natural environments.

Finally, brand and quality are also important factors. Choosing well-known brands and reliable quality isolating switches can ensure stable performance, a long service life, and reduce equipment failures and maintenance costs.

 

Q: How to maintain to extend the service life of the isolating switch?

A: Test the switching function monthly, clean the dust on the shell, and check whether the contacts are oxidized. Each year, have the manufacturer's engineers calibrate the mechanical interlock, upgrade the frequency converter program, and replace worn parts.

 

Visit our SDKC Isolating Switch production workshop

 

Our company is always committed to providing customers with high-quality electrical component products and excellent services. Our Isolating switch 3P has won the trust and support of many customers with its excellent performance, reliable quality, and perfect after-sales guarantee. If you are interested in our products or have any questions, please feel free to contact us. We look forward to working with you to create a better future for the power industry.

 

Hot Tags: isolating switch 3p, China isolating switch 3p manufacturers, suppliers, factory, 63a switch fuse isolator, ac22a main switch, electric switch disconnector, automatic isolator switch, two pole isolator switch, 125a switch disconnector


 

Send Inquiry