Do You Know The Steps For Troubleshooting Motor Faults? (II)
Aug 02, 2025
Leave a message
Do you know the steps for troubleshooting motor faults? (II)
III. Electrical Testing (Instrumentation Required)
1. Winding Resistance Measurement (Ohmmeter - Multimeter/Microohmmeter):
- Disconnect all external connections (including ground and PE wires).
- Measure the interphase resistance of the three-phase windings (U1-U2, V1-V2, and W1-W2).
Judgment:
- The three-phase resistance values should be very close (the difference generally does not exceed 2% of the average value). Unbalanced windings may have a short circuit, an open circuit, or a poor connection.
- Infinite resistance (∞): The winding is open (broken wire).
- Resistance significantly lower than normal or zero: The winding is severely shorted (further confirmation with a megohmmeter or bridge is required).
- Single-phase motor: Measure the resistance of the main and auxiliary windings (starting windings) and compare them to the rated value or a known normal value. Check whether the centrifugal switch (if installed) is functioning properly.
2. Insulation Resistance Measurement (Megger):
- Select a megohmmeter with an appropriate voltage rating (e.g., 500V DC for low-voltage motors).
Measurement Items:
- Winding-to-ground insulation: Measure each winding phase (U, V, W) against the motor housing (ground terminal).
- Phase-to-phase insulation: Measure between U-V, V-W, and W-U.
Determination (Refer to standards or motor nameplates, common low-voltage motor requirements):
- Cold insulation resistance should generally be > 5 MQ.
- Hot insulation resistance should be > 1 MQ.
- Measured values significantly below the required value or continuously decreasing indicate insulation moisture, aging, contamination, or damage.
- Close to zero: A serious ground fault.
Note: When measuring, leave the megohmmeter leads hanging; do not touch them. Record the reading after it stabilizes (usually the value after 60 seconds).
3. Power Supply and Connection Inspection (Power-Off Inspection):
- Check the condition of the main power circuit breaker, contactor, thermal relay, and fuse.
- Tightness Inspection: Use a torque wrench (if available) or other suitable tool to check the tightness of all power terminals (motor and power supply sides) and the ground terminal to ensure they are not loose, corroded, or oxidized.
- Cable Inspection: Inspect the power cables for damage, aging, or signs of overheating.
4. Voltage and Current Measurement (Power-On Inspection - Extremely Careful!):
- Ensure safety is ensured, energize the motor (start with no load or light load).
- Three-Phase Voltage Measurement: Measure the line voltages between U-V, V-W, and W-U at the motor terminals. They should be balanced and close to the rated voltage (difference <1%).
- Three-Phase Current Measurement: Use a clamp ammeter to measure the currents of the U, V, and W phases respectively. Diagnosis: The three-phase no-load current should be balanced (difference less than 10%) and close to the no-load current value on the motor nameplate (if no current is shown, it should be approximately 30%-50% of the rated current).
- Current imbalance: This may be caused by unbalanced power supply voltage, winding fault (turn-to-turn short circuit), uneven air gap, broken rotor bars, bearing problems, or uneven load.
- Excessive current: This may be caused by overload, mechanical jamming, bearing damage, low voltage, winding short circuit (phase-to-phase or turn-to-turn), broken rotor bars, or single-phasing (two phases with zero current in one phase).
- Undercurrent: This may be caused by load loss, power phase loss (zero current in one phase), or incorrect winding connections.