How To Achieve Selective Protection Between Series Circuit Breakers?
Sep 16, 2023
Leave a message
In order to achieve selective protection of series circuit breaker devices, their respective operating current setting values and action delays must be reas
onably selected so that they can operate in a certain sequence. There are two methods commonly used:
1. Use the classification of the operating current of the overcurrent release to achieve selectivity: This is only possible when the expected short-circuit current values of the upper and lower circuit breakers are very different. That is to say, the operating current setting value of the upper-level circuit breaker must be higher than the maximum expected short-circuit current value at the installation location of the lower-level circuit breaker.
2. Use short-delay overcurrent releases to achieve selectivity: If the impedance of the connecting conductor is very low and the expected short-circuit current at the installation location of the upper and lower circuit breakers is very different, you can only add a short delay action to the upper and lower circuit breakers. An overcurrent release is used to meet the selectivity requirements, and its delay time should ensure that the lower-level circuit breaker can break the short-circuit current.
The fixed classification of delay time is: 150ms for electromagnetic release and 70ms for electronic release. Such short time delay releases meet selectivity requirements. The minimum operating current setting value of the short-time delay release must be equal to 1.25 times the operating current of the downstream circuit breaker.
In addition, an instantaneous release can be equipped in addition to the time-delay release to improve the dynamic and thermal stability of the upper-level circuit breaker in the event of a full short circuit. Its setting value should ensure that it can operate during a total short circuit without being interfered by selective actions.