Distribution Box Labeling And Wiring
Apr 29, 2026
Leave a message

I. Distribution Box Labeling Standards
Labels must be clear, accurate, and durable, and mainly include the following:
1. External Labeling
Safety Warning Sign: Must be affixed with "Caution: Electric Shock," a yellow background with a black triangle lightning bolt symbol, in a prominent position.
Distribution Box Nameplate: Name, model, serial number, protection level, rated voltage/current.
Responsibility Sign: Indicates the person responsible for maintenance and their contact number, affixed to a commonly used location in the upper left corner of the box.
Circuit Purpose Labeling: Indicates the power supply area or equipment name on the outside of the box door, such as "Building A Lighting" or "Air Compressor No. 1."
2. Internal Labeling
System Diagram: Affixed to the inside of the door, including the main switch, branch switches, wire specifications, circuit number, Pe/Kx/Ijs, etc.
Each Switch/Circuit Labeling: Indicates the purpose below or on the side of each branch switch, such as "Lighting Circuit" or "Socket Circuit." Label printing is recommended for clear and durable lettering.
N-line terminal blocks and PE-line terminal blocks: These must be labeled "N" and "PE" or "Neutral" and "Protective Grounding" respectively.
Cable tags: Tag both ends of the incoming and outgoing cables, indicating the cable number, specifications, and start/end point.
II. Distribution Box Wiring Standards
1. Wire Colors
L1 (Phase A): Yellow, no other colors allowed.
L2 (Phase B): Green, no other colors allowed.
L3 (Phase C): Red, no other colors allowed.
N (Neutral): Light blue, must not be mixed with PE.
PE (Protective Earth): Yellow/green, must not be used as a phase or neutral wire under any circumstances.
2. Terminal Blocks and Wiring
N Block: Insulated installation, all neutral wires are concentrated here. Only one wire is allowed to be crimped into each terminal block unless the manufacturer explicitly allows two.
PE Block: Directly connected to the box and grounding mains. One wire per terminal block.
Multi-strand flexible wire: Cold-pressed terminals must be used; do not insert the wire directly into the terminal screw after tightening.
3. Special Scenarios
Socket Circuit: Must be connected to a residual current device (RCD). N and PE must not be short-circuited behind the socket. Lighting circuit: If using LED drivers, ensure the neutral line is not shared, as this can easily cause flickering or false tripping due to leakage.
Three-phase motor circuit: The phase sequence must be correct; forward and reverse rotation can be achieved by swapping any two phases.
